AUTOMATIC
FIRE DETECTION AND ALARM SYSTEM AND HIGH VELOCITY WATER SPRAY SYSTEM
SCOPE
This section covers the requirements of fire detection and
alarm system (FDA) for substation building, high velocity water spray system
for transformer bays
DESIGN BASIS FOR FDA SYSTEM
1.
FDA
system shall include but not be limited to the following areas :-
2.
Control
room
3.
MV
& LV switchgear rooms
4.
Cable
vault
5.
220/11KV,
conversion & rectifier transformers in outdoor switchyard.
The
computer aided microprocessor based intelligent type FDA system shall be a software controlled
automatic system and shall provide necessary programmed activities and various
controls.
Fire Extinguishers
Portable/Mobile Fire Extinguishers
and Fire Buckets shall be provided for all the areas as per IS-2190.
DESIGN BASIS FOR HIGH VELOCITY WATER
SPRAY SYSTEM
- An
automatic HVWS system with quartzoid bulb shall be provided for the
outdoor transformers along with detection network. The system shall be
designed in such a manner that when
the surrounding temperature surpasses the set value, the quartzoid bulb
will explode, thereby giving an indication in the control panel, which in
turn will initiate the water sprinkler system.
- High
velocity water spray system shall be provided for the Transformer.
Complete impingement on all exterior surfaces of the Transformer shall
have to be protected. Where there is insufficient space to install water
spray nozzles underneath transformer, horizontal projection shall be
provided to protect the entire surfaces underneath the transformer.
Transformer shall be protected using ring of nozzles including the top of
the transformer
- Automatic
detection equipment shall be so located and adjusted as to operate
reliably. For transformer the detector sprinklers shall be as close to the
shell as possible at all places subject to electrical clearance.
- There
shall be a ring of detectors around the top of the transformer and a
second ring around the base. Continuous ring mains shall be avoided.
EQUIPMENT DETAILS
FDA System
The system shall include the
following :-
·
Addressable/intelligent
type ionization detectors.
·
Addressable/intelligent
type photo-electric detectors.
·
Addressable/intelligent
type fire alarm panel with battery and in-built printer located in SCADA room.
·
Addressable/intelligent
type manual call point
·
Electronic
hooters (Addressable)
·
Response
indicators
·
Control
module (Addressable)
·
Monitor
module (Addressable)
·
Relay/contracts
·
Control
cables
·
Special
cables
Addressable Intelligent Ionisation
Type Smoke Detector
Ionisation
smoke detector shall be self compensating the effects of air temperature,
humidity dust and atmospheric pressure. Each detector shall have built-in
microprocessor and it shall be possible to change the sensitivity of each
detector from fire alarm panel.
Addressable Intelligent Photo
Electric Type Smoke Detector
The
photo electric smoke detector shall automatically adjust to compensate for
possible effects of dirt and dust accumulation. The detector shall have
built-in microprocessor and it shall be possible to change the sensitivity of
each detector from control panel.
Addressable Intelligent Type Heat
Detectors
Heat
detectors shall be quick response and use rate of rise/fixed temperature
principle. The detector shall automatically adjust to compensate for possible
effects of change in ambient temperature.
Remote
Response Indicator
·
One remote response indicator shall
be provided for each detector located above the false ceiling/false floor. The
remote response indicator shall be suitable for false ceiling/wall mounting and
provided with a light emitting diode for alarm state indication.
·
Adequate slack shall be available in
the cable connecting the remote indicator to the detector so as to allow ease
of dismantling the false ceiling/false floor without damaging the remote
response indicator/false ceiling/false floor panel.
Addressable
Interface Unit
The
interface unit shall be suitable for initiating devices such as manual call
point, pressure switch, flow switches, level switches, potential fire contacts
etc. in the addressable loop.
Electronic
hooter
The hooter
shall have distinctive tones with different frequencies for indication of
first, second fire alarm and fault alarm. After ‘acknowledgement’ of alarm the
hooter shall silence and a “Buzzer” shall give “beep tone” till the alarm
condition persists.
Manual
Call Push-button Station:(Addressable/Intelligent)
Manual call
push button station shall preferably be of the manual break-glass type which
shall automatically signal an alarm on break of the glass
Micro-processor
Based-intelligent Fire Alarm Control Panel
Fire alarm
control panel shall function as communication interface between Central
Processing Unit and sensors and controlled devices. Control panel shall be
intelligent, each with its own microcomputer and memory.
Cables
All type of
special cables required for the fire detection and alarm system shall be
provided.
High
Velocity Water Spray System
The
system shall include, but not be limited to the following :-
·
Electric Motor driven pump
·
Diesel Engine driven pump
·
Jockey pump
·
Deluge Valves
·
Spray Nozzles (Open type)
·
Pipe & Fittings
·
Gate Valves, Non-return Valves,
Isolating Valves etc.
·
Piping Network including supports,
instruments etc as required
·
Detection system
Pump
House & Reservoir
A common
pump house with equipment handling facilities shall be provided for high
velocity water spray system, fire hydrant system as well as drinking and
sanitation water system. The civil works for the pump house will not be in
scope of SIEMENS. Siemens will provide and install one no. motor driven pump,
one no. diesel driven pump and one no. jockey pump in the pump house.