Basics of Conditional monitoring of power transformer

Types of monitoring

  • Behavior monitoring
  • Periodic monitoring
  • Online monitoring
  • Diagnostic monitoring
Behavior monitoring
  • Operating temperatures
  • Noise level
  • Oil levels
  • Flow indicators
Periodic monitoring
  • Impedance measurement
  • Capacitance& tan delta of windings /bushings
  • No load losses
  • Magnetic balance
  • Mag current
  • Oil tests
  • Dissolved gas analysis
Oil tests
  • Breakdown voltage
  • Moisture content
  • Acidity
  • Tan delta
  • resistivity
Dissolved gas analysis
  • Type of fault gasses
  • H2  partial discharges
  • Co   cellulose involvement
  • C2 h2     acetylene  arcing
  • Ch4 , c2h4, c2h6,  thermal hot spots
  • Frequency of DGA
  • Decision on investigation
Online monitoring
  • Online dga
  • Online PD
Diagnostic monitoring
  • Low voltage tests
  • Loss measurement
  • Voltage ratio
  • Resistance
  • Frequency response analysis
  • Degree of polymerization index
  • Furan analysis (furfural content)
Frequency response analysis
  • To detect movement of windings under short circuit conditions
  • Low voltage sinusoidal output to one end of winding from network analyser
  • Voltage transfer function measured from 5hz to 10mhz
  • NA programmed to measure amplitude  and phase shift at discreet intervals of frequencies
  • Condition assessment based on
      1. Comparison  of responses from different phases for each winding and tap position
       2. Comparison of responses from different transformer of the same design response comparison
  • Response for all three phases to be similar on a particular tap position for a single transformer and for different transformer of same design
  • Appearance of new features or major phse shift is concern.
  • Transformer windings LC  network responses governed by inductance/capacitance of network
Frequency bandwidths
  • 5hz  to 2khz indicate mag circuit condition
  • 2khz  to 200 khz   changes in leakage impedance
  • 1mhz and above  indicate capacitance changes
DP INDEX
  •  Kraft paper used as insulation is a mat of cellulose fibers which consist of cellulose molecules
  • Cellulose a linear polymer of glucose molecules that are linked by glycosidic bonds.
  • Length cellulose molecule is measured in terms of DP Index.
Mechanical strength  of paper
  • Depends on dpindex of paper
  • New paper   1200 to 2000
  • Below 250  a matter of concern
  • Below 150 little life left and close to failure
Furfural analysis
  • Product of cellulose  degradation are furan compounds particularly 2-furfural dehyde
  • Compounds stable up to 110 degree centigrade
  • Presence of compounds in oil is certain indication of cellulose degradation


5 comments:

Dilip said...

Thanks for sharing nice concept on Basics of Power Transformer in India. I hope this blog will help most of the people who are using power transformers. Thanks a lot!

webbingindia said...

Great information, thanks for sharing.
electrical transformers and services

webbingindia said...

Thanks for the article, keep sharing.
11kv combined ct-pt unit

vajra said...
This comment has been removed by the author.
Anonymous said...

Thanks for sharing of transfer, motor and generator post. good explanation of this blog. Please keep sharing.

Chitika