Basics of Conditional monitoring of power transformer

Types of monitoring

  • Behavior monitoring
  • Periodic monitoring
  • Online monitoring
  • Diagnostic monitoring
Behavior monitoring
  • Operating temperatures
  • Noise level
  • Oil levels
  • Flow indicators
Periodic monitoring
  • Impedance measurement
  • Capacitance& tan delta of windings /bushings
  • No load losses
  • Magnetic balance
  • Mag current
  • Oil tests
  • Dissolved gas analysis
Oil tests
  • Breakdown voltage
  • Moisture content
  • Acidity
  • Tan delta
  • resistivity
Dissolved gas analysis
  • Type of fault gasses
  • H2  partial discharges
  • Co   cellulose involvement
  • C2 h2     acetylene  arcing
  • Ch4 , c2h4, c2h6,  thermal hot spots
  • Frequency of DGA
  • Decision on investigation
Online monitoring
  • Online dga
  • Online PD
Diagnostic monitoring
  • Low voltage tests
  • Loss measurement
  • Voltage ratio
  • Resistance
  • Frequency response analysis
  • Degree of polymerization index
  • Furan analysis (furfural content)
Frequency response analysis
  • To detect movement of windings under short circuit conditions
  • Low voltage sinusoidal output to one end of winding from network analyser
  • Voltage transfer function measured from 5hz to 10mhz
  • NA programmed to measure amplitude  and phase shift at discreet intervals of frequencies
  • Condition assessment based on
      1. Comparison  of responses from different phases for each winding and tap position
       2. Comparison of responses from different transformer of the same design response comparison
  • Response for all three phases to be similar on a particular tap position for a single transformer and for different transformer of same design
  • Appearance of new features or major phse shift is concern.
  • Transformer windings LC  network responses governed by inductance/capacitance of network
Frequency bandwidths
  • 5hz  to 2khz indicate mag circuit condition
  • 2khz  to 200 khz   changes in leakage impedance
  • 1mhz and above  indicate capacitance changes
DP INDEX
  •  Kraft paper used as insulation is a mat of cellulose fibers which consist of cellulose molecules
  • Cellulose a linear polymer of glucose molecules that are linked by glycosidic bonds.
  • Length cellulose molecule is measured in terms of DP Index.
Mechanical strength  of paper
  • Depends on dpindex of paper
  • New paper   1200 to 2000
  • Below 250  a matter of concern
  • Below 150 little life left and close to failure
Furfural analysis
  • Product of cellulose  degradation are furan compounds particularly 2-furfural dehyde
  • Compounds stable up to 110 degree centigrade
  • Presence of compounds in oil is certain indication of cellulose degradation