PLCC system
uses the same High Voltage transmission line connecting two sub-stations for
telecommunication purpose too.
PLCC is used in all power utilities as
a primary communication service to transmit speech, telemetry and protection
tripping commands. This is economic and reliable for message transfer as well
as low bit rate RTU signals.
PLCC
1. The voice/data are mixed with radio frequency carrier (40-500kHz),
amplified to a level of 10-80W RF power and injected in to high voltage power
line using a suitable coupling capacitor.
2. The power line as a rigid long conductor parallel to ground, guides the
carrier waves to travel along the transmission line.
3. Point to point communication takes place between two SSB transceivers at
both ends.
4.
The
signal that can be transmitted over the PLCC include
•
Speech signals
•
Data/Telemetry signals
• Signals required for Tele
protection.
Importance
of PLCC
1.
PLCC
is used for conveying these information without any interference with normal
power flow.
2.
The
concept of GRID has been developed for the effective utilization of available
electrical energy.
3.
Load
Despatch centre will be required to monitor & control the electrical
network.
4.
The
LD centre have to process & act upon data (MW,MVAR, KV etc).
History
The first PLCC system was introduced
by an American company in 1920.
The power line conductors were used
for communication instead of separate
telephone lines.
In India PLCC system was introduced
for speech & protection in 1950.
Line
trap or Wave Trap(WT)
·
Name
itself suggests that it traps the waves /frequencies of High magnitude.(50 KHz
to 500 KHz)
·
WTs
are provided to block the carrier signals from entering in the sub-station and
to allow the power frequency current to pass through.
·
Achieved
by providing a suitable filter consisting capacitors & inductors.
·
L.
A. is provided across WT to protect it from high voltages surges.
Working
Principle
- PLCC
works on Modulation & Demodulation.
- Modulation
& Demodulation requires carrier frequency which is generated in in
cabinet.
- Crystal
Oscillator generates carrier frequency.
- PLCC
panel/terminal/cabinet/set consists of Audio Frequency (AF )section
Transmit
path
- The
speech signal along with other Voice
- Frequency
signals is fed to IF modulator.
• IF modulator modulates the AF signals to IF
stage.
• Up converter converts IF to HF.
• HF signal is fed to preamplifier & then
to Power amplifier t raise the output level t required value.
• The amplified signals are then fed to HF
hybrid.
• Hybrid is used to provide isolation between
Tx & Rx path at HF stage.
• HF signals are then connected to HF Cable.
Receive
Path
·
The receive section receive the signals from remote
end through HF Hybrid.
·
Down-Converter converts the signals from HF to IF
in connection with a band pass filter which allow only the required signals having
a certain band.
·
Demodulator demodulate the signals from IF to AF.
·
Speech, data & other superimposed channels are
separated out with suitable filters,
Importance
of Pilot
A pilot frequency is provided for
self-monitoring & Automatic Gain control (receiver volume control).
• Pilot indicates the healthiness of
cabinets.
• Pilot freq.is transmitted during normal
rest condition & shifted dial is transmitted during dialing for transmission
of pulses.
• A dc signal whose amplitude is proportional
to receive signal is fed to the amplifier in Rx section to control the gain of
the amplifier.
Frequency
allocation in PLCC
·
HF
band 50 KHz to 500 KHz
·
Voice Frequency 0.8 to 1 KHz.
·
Data channel freq. called as AF 1 to 4 KHz.
·
Pilot
freq. 2.5 to 4 KHz.
·
IF 24 to 28 KHz.
·
Bandwidth 4 or 8 KHz
Coupling
Capacitor
Offers isolation between the high voltage
line and carrier equipment.
•
It
offers minimum impedance to carrier frequencies (50 KHz to 500 KHz)and high
impedance to power frequency( 50 Hz).
•
The
top end of C.C. is connected to the high voltage line and lower end is connected
to the earth through LMU.
Specifications
of WT & CC
Wave Trap
•
2000A/ 1.0 mH
•
1250 A/ 0.5 mH
•
630 A / 0.5 mH
•
Tuning pot
•
Freq. Band
•
Blocking impedance
•
Blocking Resistance
Coupling Capacitor
• Rated capacitance:-
– 400 kV-4400pf
– 220 kV-6600pf
• Attenuation in dB:-0.5 dB
• Pass Band- 50 to 500 kHz
Connection of WT & CC
Line
Matching Unit
Name itself gives idea that this unit
matches something. This something is nothing but Line impedance.
• It is mounted at the base of the coupling
Capacitor.
• LMU consist of 2 units called unit A &
unit B
• Unit A consist of
– Balancing T/F
– Matching T/F
– Filter unit.
• Unit B consist of
– Matching T/F
– Filter unit.
Balancing
Transformer
–
It improvises better Ph. Splitting & couples the o/p of PLCT to the
coupling filters.
–
It ensures the carrier signals are in healthy condition even under the failure
of any of the coupled phases & voltage isolation.
•
Matching Transformer
–
Impedance matching & high voltage isolation.
•
Capacitor Filter together with CC forms
Three
element protective device
Lightening Arrestor
– Protects coupling device from high voltage
spikes from power line that appear at the bottom of coupling condenser.
• Drainage Coil Offers low impedance
to power frequency and high impedance to carrier frequencies, thereby power
frequency current flowing through coupling condenser gets grounded and protects
the coupling device.
• Earth switch
– Normally this is kept open but is
closed
Technical
specifications
LMU
– Operating Band width- 80-500 KHz for
CC 4400 pf.
– Composite loss- < 2db.
– Return loss > 12 db
– Equipment side Impedance- 75 Ohm
– Line side Impedance- 600 Ohm ph. to
Ph.
– Peak envelope power- 650 W
LA
– Rated Volt.- 850 V
– P.F. spark Over Volt.- Twice rated
Volt.
Drainage Coil
- Rated
Inductance- 40 mH
- Cont.
Current rating- 1 Amp.
- Short
time current rating- 50 Amps.
Earth Switch
– insulation withstand Volt.- 10 KV AC
– Rated current- 400 Amps
4 comments: