A
typical 132kV double bus generating station is made up of two 100MVA generators
and associated step-up transformers, providing power to the high voltage
system, by means of four overhead transmission lines. If the main bus is
sectionalised with a bus section circuit breaker and the reserve bus is split
by bus section isolators, calculate for a high impedance circulating current
scheme having 4 zones and an overall check feature, as follows :-
1.
The stability level of the busbar protection.
2.
The discriminating and check features primary
fault settings.
3.
The value of stabilising resistor required
with the MCAG14 relay whose current setting range is 0.2 – 0.8A and has a
burden of 1VA at the current setting.
4.
The supervision relay primary setting, using
a VTX31 with a voltage setting range of 2 – 14 volts. Assume the relay burden
at the setting is 2 milli VA.
5.
Determine the CT knee point voltage
requirements.
Given
that the switchgear rating is 3500MVA, the system voltage is 132kV solidly
earthed, the maximum pilot resistance is 4 ohms and that the non-linear
resistors to be connected across the buswires to limit the peak volts follow
the expression V=900I0.25. The current transformers are of ratio
500/1 amp, have a secondary internal resistance of 0.7 ohms and have a
magnetising impedance of 2000 ohms.
The
layout of the station is a shown in the diagram.
Solution:
1.
The stability level of the busbar protection
is governed by the switchgear rating which in this instance is
= 15300 Amps
= 15300 Amps
2.
The primary operating current of busbar
protection is normally between 2% and 10% of the stability level i.e. between
306 amps and 1530 amps. Where 30% of the minimum fault current is more than the
full load current of the largest circuit, the primary operating current should
be made more than the full load current i.e. 130% of full load current.
Full load current =
Full load current =
\ Primary operating current = 1.3 x 438
= 569 Amps
Discriminating Feature
Relay voltage setting = =
= 144 volts
Magnetising current taken by each C.T. at 144 volts
=
= 0.072 Amps
Metrosil r.m.s. current at 144V is given by:
= = 1.36mA
In practice the metrosil current is considered to be negligible and is ignored.
To obtain a primary operating current of 569 amps the relay current setting must be calculated as follows :-
Primary operating current = CT ratio (IRELAY + n.ICT)
Where n = maximum number of CT’s per zone (i.e. 5)
\ IRELAY === 0.778A
The nearest available setting is 0.8A.
This gives an actual primary operating current of :-
Primary operating current = 500 (0.8 + 5 x 0.072)
= 500 x 1.16
= 580 Amps
Check Feature
Relay setting voltage = 144 volts
Relay setting current (Is) = 0.8 Amps
Maximum number of circuits = 6
Primary operating current = 500 (0.8 + 6 x 0.072)
= 500 x 1.232
= 616 Amps
4.
Voltage setting of the supervision relay Vsp
= I (R // Zm)
R = Rst + Rr = resistance of stabilising resistor and relay
Zm = parallel impedance of CT magnetising impedances assuming 1 CT is open circuit
I = supervision operating current
Whenever possible the supervision primary operating current should not be more than 25 amps or 10% of the smallest circuit, whichever is the greater.
For the discriminating zone there are 5 CT’s. Therefore assuming one CT is open circuit :-
Zm =
R = Rst + Rr = resistance of stabilising resistor and relay
Zm = parallel impedance of CT magnetising impedances assuming 1 CT is open circuit
I = supervision operating current
Whenever possible the supervision primary operating current should not be more than 25 amps or 10% of the smallest circuit, whichever is the greater.
For the discriminating zone there are 5 CT’s. Therefore assuming one CT is open circuit :-
Zm =
R = Rst + Rr = 178.44 + = 180 ohms
Assuming I = 25 amps
V =
For the check zone there are 6 CT’s. Therefore assuming one CT is open circuit
Zm = = 400 ohms
V = = 6.2V
5.
Knee point voltage of the current
transformers should not be less than twice the relay setting voltage.
VK = 2 x 144
= 288 volts
VK = 2 x 144
= 288 volts
No comments:
Post a Comment