Sunday, February 16, 2014

Directional Earth fault

Step 1: Operating signal & polarizing signal

Requirements are similar to directional overcurrent 
i.e.       need operating signal
            and polarising signal

Operating Signal
obtained from residual connection of line CT's
i.e.       Iop  =  3Io
Polarising Signal
The use of either phase-neutral or phase-phase voltage as the reference becomes inappropriate for the comparison with residual current.
Most appropriate polarising signal is the residual voltage.


Residual Voltage

Notes :
1.         VT primary must be earthed.
2.         VT must be of the '5 limb' construction (or 3 x single phase units)


Step 2: Relay Characteristic Angle

0  -  Resistance earthed systems
45 (I lags V)  -  Distribution systems (solidly earthed)
60 (I lags V)  -  Transmission systems (solidly earthed)

Current Polarising
A solidly earthed, high fault level (low source impedance) system may result in a small value of residual voltage at the relaying point.  If residual voltage is too low to provide a reliable polarising signal then a current polarising signal may be used as an alternative.
The current polarising signal may be derived from a CT located in a suitable system neutral to earth connection.
e.g.

No comments:

Chitika