Carrier Communication Schemes:-
The main disadvantage
of conventional time-stepped distance protection is that the instantaneous
Zone-1 of the protective scheme at each end of the protected line is set to
cover 80% of the line and hence faults in the balance 20% of the line (at each
end) are cleared in Zone-2 time, which is undesirable.
The desirable scheme
is the one wherein the relays clear the faults on the 100% of the protected
line instantaneously and also provide backup for uncleared faults on adjacent
lines. This can be achieved by
interconnecting the distance relays are each end of the line by a signaling
channel (which can be either pilots, a power line carrier communication channel,
a radio link or a microwave channel).
The purpose of the
signaling channel is to transmit the information about the system conditions at
one end of the protected line to the other end and initiate or prevent tripping
of the remote circuit breaker. The former
arrangement is referred to as a “Transfer trip scheme” while the latter is
known as “Blocking scheme”
a) Transfer
trip scheme:-
In this scheme, the distance relay
at one end of the protected lines sends a carrier signal to the relay at other
end of the line for inter-tripping, thereby clearing the faults on entire line
instantaneously.
Transfer trip is of
two types:-
i)
Under-reaching scheme:
The scheme in which
the Zone-1 relay (set to cover about 80% of ZL) is used to send a signal to the
remote end of the feeder for inter-tripping is termed as transfer trip
under-reaching scheme. To avoid
mal-operation due to receipt of false signal, the receiving end relay operation
is inter-locked with its Zone-3/starter operation i.e. the scheme operates
either by its own Zone-1 relay operation or by receipt of carried and its
Zone-3/starter operation.
ii)
Over-reaching scheme:-
This scheme is
suitable for short lines where an underreaching Zone-1 would be too short to be
of any practical use. In this scheme the
relay set to reach beyond 100% of the
line, is used to send an inter-tripping signal to the remote end of the
line. It is essential that the receive
relay contact be monitored by a directional relay to ensure that tripping does
not take place unless the fault is within the protected section. The disadvantage of this scheme is that there
is no independent Zone-1 tripping. The
fast tripping therefore relies entirely on signaling channel.
The disadvantages of
these schemes is that the signal is transmitted over the fault line
section. Distortion of the signal may
occur due to attenuation introduced into the line by the fault.
b) Blocking schemes:-
In this scheme, a
blocking signal is sent by the reverse looking directional unit ZR to prevent
instantaneous tripping for Zone-2 & Zone-3 faults, external to the
protected line. Here ZR must operate
faster then forward looking Zone-3 units and the signaling channel must also be
extremely fast is operation.
Though all the distance schemes with carrier
inter-tripping/carrier blocking facility are procured, the same are yet to be
commissioned.
No comments:
Post a Comment