FOR 89-A/BAY ISOLATOR OPERATION:
- 52 CB/BAY IN OPEN CONDITION.
- 89AE/BAY EARTH SWITCH OPEN CONDITION.
- 89LE1/BAY EARTH SWITCH OPEN CONDITION.
- BB189E BUSEARTH SWITCH OPEN CONDITION
FOR 89-L ISOLATOR OPERATION:
1.52 CB IN OPEN
CONDITION.
2.89AE EARTH SWITCH
OPEN CONDITION.
3.89LE1 EARTH SWITCH
OPEN CONDITION.
4.89LE2 LINE EARTH
SWITCH OPEN CONDITION.
FOR 89-AE EARTH SWITCH OPERATION:
1.89-A ISOLATOR OPEN
CONDITION.
2.89-L ISOLATOR OPEN
CONDITION.
FOR 89-LE1 EARTH SWITCH OPERATION:
1.89-A ISOLATOR OPEN
CONDITION.
2.89-L ISOLATOR OPEN
CONDITION.
FOR 89-LE2 EARTH SWITCH OPERATION:
1.89C BUS ISOLATOR OPEN
CONDITION.
2.89L LINE ISOLATOR
OPEN CONDITION.
3.LINE DEAD CONDITION i.e U/V RELAY OPERATED.
FOR 52 CB CIRCUIT BREAKER FOR REMOTE
OPERATION:
1.86-GA HSTR/MTR RESET CONDITION.
2.86-GB HSTR/MTR RESET CONDITION.
3.96-BB TBC HSTR/MTR RESET CONDITION.
FOR 52 CB CIRCUIT BREAKER FOR LOCAL
OPERATION:
1. 89-A ISOLATOR OPEN
CONDITION.
2. 89-L ISOLATOR OPEN CONDITION.
3. 89-AE
TBC EARTH SWITCH CLOSED CONDITION.
4. 89-LE1 EARTH SWITCH CLOSED CONDITION.
FOR 89-C ISOLATOR OPERATION:
1.NO OTHER ISOLATOR IS
CLOSED TO TRANSFER BUS C
2.BB389E EARTH SWITCH
OPEN CONDITION.
3.89LE2 EARTH SWITCH
OPEN CONDITION.
4.52 TBC CB IN OPEN CONDITION.
OR
1.52 CB IN CLOSED
POSITION.
2.89-A ISOLATOR CLOSED
CONDITION.
3.89-L ISOLATOR CLOSED
POSITION.
4.89-A/TBC BAY BUS-A
ISOLATOR CLOSED POSITION.
5.89-C/TBC BAY BUS-C
ISOLATOR CLOSED POSITION.
6.NO OTHER ISOLATOR IS
CLOSED TO TRANSFER BUS C
7.ADDITIONAL INTERLOCK
PROTECTION TRANSFERRED MAY ALSO PUT THROUGH PROTECTION TRANSFER SWITCH.
TRANSFER BUS COUPLER
FOR 89-A / TBC ISOLATOR OPERATION:
1.52 CB / TBC IN OPEN
CONDITION.
2.89AE / TBC EARTH
SWITCH OPEN CONDITION.
3.89CE / TBC EARTH
SWITCH OPEN CONDITION.
4.BB189E BUSEARTH
SWITCH OPEN CONDITION.
FOR 89-C / TBC ISOLATOR OPERATION:
1.52 CB / TBC IN OPEN
CONDITION.
2.89AE / TBC EARTH
SWITCH OPEN CONDITION.
3.89CE / TBC EARTH
SWITCH OPEN CONDITION.
4.BB389E BUSEARTH
SWITCH OPEN CONDITION.
FOR 89-AE / TBC EARTH SWITCH OPERATION:
1.89-A / TBC ISOLATOR
OPEN CONDITION.
2. 89-C / TBC ISOLATOR
OPEN CONDITION.
FOR 89-CE / TBC EARTH SWITCH OPERATION:
1.89-A / TBC ISOLATOR
OPEN CONDITION.
2. 89-C / TBC ISOLATOR
OPEN CONDITION
FOR 52 CB / TBC CIRCUIT BREAKER FOR
REMOTE OPERATION:
1.86-GA / TBC HSTR/MTR
RESET CONDITION.
2.86-GB / TBC HSTR/MTR
RESET CONDITION.
3.96-BB / TBC HSTR/MTR
RESET CONDITION.
FOR 52 CB / TBC CIRCUIT BREAKER FOR
LOCAL OPERATION:
1. 89-A / TBC ISOLATOR
OPEN CONDITION.
2. 89-C / TBC ISOLATOR
OPEN CONDITION.
3. 89-AE / TBC EARTH SWITCH CLOSED CONDITION.
4. 89-CE / TBC EARTH SWITCH CLOSED CONDITION.