CIRCUIT BREAKERS
The
function of a Circuit breaker is to isolate the faulty part of the power system
in case of abnormal conditions.
A
Circuit breaker has two contacts - a fixed contact and a moving contact. Under
normal conditions these two contacts remain in closed position. When the
circuit breaker is required to isolate the faulty part, the moving contact
moves to interrupt the circuit. On the separation of the contacts, the flow of
current is interrupted, resulting in the formation of arc between the contacts.
The contacts are placed in a closed chamber containing some insulating medium
(liquid or gas) which extinguishes the arc.
Arc Interruptions
There are two methods of arc interruption
i.
High
Resistance Interruption
ii. Current Zero Interruption
(i) High
Resistance Interruption
In this method of arc interruption,
its resistance is increased so as to reduce the current to a value insufficient
to maintain the arc. The arc resistance can be increased by cooling,
lengthening, constraining and splitting the arc. This method is not suitable
for a large current interruption.
(ii) Current
Zero Interruption
In case of a.c
supply, the current wave passes through a zero point, 100 times per second at
the supply frequency of 50 Hz. This feature of arc is utilised for arc
interruption. The current is not interrupted at any point other than the zero
current instant, otherwise a high transient voltage will occur across the
contact gap.
Restriking voltage and Recovery Voltage
After the arc has been extinguished, the voltage
across the breaker terminals does not normalise instantaneously but it
oscillates and there is a transient condition. The transient voltage which
appears across the breaker contacts at the instant of arc being extinguished is
known as restriking voltage. The power frequency rms voltage, which appears
across the breaker contacts after the arc is finally extinguished and transient
oscillations die out, is called recovery voltage.
Classification of Circuit Breakers
Depending
on the arc quenching medium employed, the following are important types of
circuit breakers.
i.
Oil Circuit
Breakers
ii. Air Blast Circuit Breakers
iii. Sulphur Hexafluoride (SF6) Circuit Breakers
iv. Vacuum Circuit Breakers
Comparison of SF6, CB & ABCB for Number of
Interrupters per Pole:
Rated Voltage KV
|
145 KV
|
245 KV
|
420 KV
|
765 KV
|
SF6 CB
|
1
|
1 or 2
|
2 or 4
|
4
|
ABCB
|
4
|
4 or 6
|
8 or 10
|
10 or 12
|
The
piston is pushed down by high pressure oil on top area of the piston
During closing stroke high pressure
oil is admitted from the bottom of piston. Piston bottom area being larger than
that on the top the differential pressure acts and the piston is pushed upwards
for closing stroke.
Rating of Circuit Breakers
Circuit breakers have the following
important ratings
i.
Breaking
Capacity
ii. Making Capacity
iii. Short-time Capacity
Breaking Capacity
The breaking capacity of a circuit breaker is of
two types.
(i) Symmetrical breaking capacity
(ii) Asymmetrical breaking capacity
(i) Symmetrical
breaking capacity
It
is the rms. Value of the ac component of the fault current that the circuit
breaker is capable of breaking under specified conditions of recovery voltage.
(ii) Asymmetrical
breaking capacity
It
is the rms value of the total current comprising of both ac and dc components
of the fault current that the circuit breaker can break under specified
conditions of recovery voltage.
Making Capacity
The
rated making current is defined as the peak value of the current (including the
dc component) in the first cycle at which a circuit breaker can be closed onto
a short circuit. Ip in Figure. is the making current.
Short-time Current Rating
The circuit breaker must be capable
of carrying short-circuit current for a short period while another circuit
breaker (in series) is clearing the fault. The rated short-time current is the
rms value (total current, both a.c. and d.c.
components) of the current that the circuit breaker can carry safely for a
specified short period.
Rated Voltage, Current and Frequency
The rated current is the rms value
of the current that a circuit breaker can carry continuously without any
temperature rise in excess of its specified limit.
The rated frequency is also
mentioned by the manufacturer. It is the frequency at which the Circuit breaker
has been designed to operate. The standard frequency is 50 Hz. If a circuit
breaker is to be used at a frequency other than its rated frequency, its
effects should be taken into consideration.
Operating Mechanism
Different manufacturers adopt one of the
following:
1. Pneumatic
2. Hydraulic
3. Spring
1. Compressed
air system for pneumatic mechanism: -
The pressure of the operating air
produced by the self-enclosed motor compressor unit is supervised by a pressure
gauge and controlled by a pressure switch (located in the breaker control
cabinet). The pressure switch has four sets of contacts each of which operates
at a different pressure level for the following functions: Start/stop, low
pressure indication, reclosure interlock, closing and opening interlock.
This type of system is provided
for each pole of 420 KV and 765 KV CB.
2. Hydraulic Mechanism: -
The hydraulic cylinder is mounted at
the base of interrupter unit and the hydraulic rod is pushed-up during closing
stroke and pushed down during opening stroke. Moving contact and puffer
cylinder are linked with the hydraulic rod.
The hydraulic oil at atmospheric
pressure from the low pressure tank is pumped into accumulators at high
pressure (310 kg/cm2). High pressure oil is used for opening and
closing operations.
During opening operation high
pressure oil from lower area of hydraulic piston is discharged into low
pressure tank by opening appropriate hydraulic valve.
3. Spring Mechanism: -
For CB upto 245 KV, spring operating
mechanism is used. The closing spring gets charged by geared motor. During
closing stroke the closing spring is discharged. It closes the breaker and also
charges the opening springs.
The Circuit breaker mechanism is
basically very simple since it comprises a motor-reducer and two springs (one
for closing and one for opening), plus their solenoid operated latching
devices.
The closing spring after having been
charged by the motor-reducer is kept ready for closing by its latching device.
As soon as energised, the closing
control coil friggers the closing latch thereby causing the closing spring to
operate the breaker to the closed position and simultaneously charge the
opening spring.
From now on, trip latch keeps the
breaker in the closed position and the opening springs ready for opening.
The compact design of the mechanism
avoids the need for the opening springs to be located close to each pole and
permits the opening operation to be performed by only one spring accommodated
in the control cabinet.
Reasons for preference of SF6 Breakers
Þ
Less number
of interrupters per pole, hence cheaper.
Þ
Maintenance
free. Very long contact life.
Þ
Reliable
Þ
Non-explosive
Þ
Does not
require compressed air system
Þ
Silent
operation
Þ
Technically superior
Performs all the required duties including line
switching, transformer switching, reactor switching, etc. without excessive
over voltages.
Easy to install, operate
& maintain.
OPENING &
CLOSING TIMES
a) Closing Time
Measurement of Circuit Breaker using Digital Time Internal Meter
To
measure the closing time of circuit breaker (i.e. the time elapsed from the
movement of the extending control supply to the Closing coil to the movement of
actual closing of the circuit breaker), the following circuit is made use of.
In this mode, NC/NO “start” and
NC/NO “stop” switches should be in ‘No’ position.
The
counter starts when the two terminals of “START” switch are shorted by closing
the D.P.D.T switch. Simultaneously the D.C supply is extended to the closing
coil of the breaker. The counter stops counting when the two terminals of
‘STOP’ switch are shorted through the ‘main contact’ of circuit breaker, as
soon as it closes and the timer displays the time interval, which is the closing
time of circuit breaker.
Hence
the principle is that the energisation of the closing coil of the circuit
breaker and starting of the counter should be simultaneous.
b) Measurement of Circuit Breaker Opening time
To
measure the opening time of circuit breaker, (i.e., the time elapsed from the
movement of extending control supply to the trip coil of the circuit breaker to
the movement of actual tripping of circuit breaker), the
following circuit is
made use of.
In this mode, NC/NO “START”
switch should be in “NO” position and NC/NO “STOP” switch should be in ‘NC’
position.
The
counter starts when the two terminals of “START” switch are shorted by closing
the D.P.D.T switch. Simultaneously the D.C supply is extended to the trip coil
of the breaker.
The
counter stops counting when the two terminals of “STOP” switch are opened with
the opening of the circuit breaker “MAIN CONTACTS”. The time internal displays
the time internal, which is the “Opening time” of circuit breaker.
Pole Discrepancy Relay:
Two cases are to be studied:
1) Three Phase Tripping.
All the thee
poles should simultaneously trip or close.
While tripping,if any one or more of the poles do not open simultaneous
with the other, after a set time (of 0.1 Sec.), the pole discrebancy relay will
give a trip command again to trip the same.
Similarly while closing the
breaker, if any of the three poles do not close simultaneous with the other,
the pole discrebancy relay, after a preset time (of 0.1 Sec.) will give a trip
command to trip the closed pole(s).
Single
phase tripping and Auto Reclosure:
While the
application principle is same as with the three phase tripping, the time
setting of the pole discrebancy relay shall be more than the dead time (of 1
Sec.) of the auto reclosure relay.
Circuit breaker operation
Analyzer: -
This
instrument helps in measurement of contact make and break times, contact travel
speeds.
1 comment:
Great Post!! I've read your blog, its very informative. I am so impressed to read this blog. thanks for sharing. More info https://www.realfindtrading.com
Post a Comment