          Illumination for substation is an important requirement for making operation possible at night.
          Scope of illumination for typical substation are:
        Outdoor Switchyard
        Control Room building
        Auxiliary building
        Street Lighting (service road within the switchyard)
          Lighting system for substation are considered as:
        Normal AC to cater lighting requirement during normal operating condition
        Emergency lighting on failure of normal AC lighting source
          DC emergency for illuminating strategic locations
          Lighting from DG system for bigger substations

How much illumination level required for substation?

          Lighting shall provide enough light depending on nature of work to be carried out. Operational lighting as per IS:3646 part-III.


What are the typical luminaries used in substation?
          Luminaries for outdoor switchyard:
        High Pressure Sodium Vapour (HPSV) luminaries with various combination of rating with high beam & narrow beam used to achieve desired illumination
        Ratings usually considered
          2X400W HPSV, 1X400W HPSV for switchyard and outdoor equipment
          2X250W HPSV, 1X250W HPSV for switchyard and outdoor equipment
          1X150W HPSV for street lighting
        High Pressure Mercury Vapour / Halogen luminaries are also taken if they specifically required by customer

Luminaries for control room:
        Indoor illumination is achieved by various types of luminaries according to the requirement and utility of various rooms.
        Room with CP/RP,  office, conference room with air conditioning and false ceiling are provided with recessed mounted 2X36W fluorescent lamp with mirror optic reflector.
        For LT room, DG, Store etc. where no false ceiling or AC provided, industrial type 2x36W fluorescent lamp is used.
        For cable cellar bulk head or industrial type 2x36W fluorescent lamp is used as per specification.
        Battery room is provided with corrosion proof industrial type 2X36W fluorescent lamp.
        For DC emergency bulk head incandescent lamps are used.

Input requirement
        Lux level to be achieved at what height
        Size of the area for outdoor and dimension of the room.
        Type of interior color in case of room

Design Calculation
        Lighting design calculation are normally carried out by the manufacturer with their in-house software.
        Calculation provides point by point illumination level by which total area illumination can be analysed.