FOR 89-C/BAY ISOLATOR OPERATION:
FOR 89-L/BAY ISOLATOR OPERATION:
FOR 89-AE/BAY ISOLATOR OPERATION:
FOR 89-LE1/BAY ISOLATOR OPERATION:
FOR 89-LE2/BAY ISOLATOR OPERATION:
FOR 52 CB/BAY CIRCUIT
BREAKER
FOR REMOTE OPERATION:
1.86-GA HSTR/MTR RESET
CONDITION.
2.86-GB HSTR/MTR RESET
CONDITION.
3.96-BB TBC HSTR/MTR
RESET CONDITION.
4.89A/89B ISOLATOR CLOSE POSITION
5.89L ISOLATOR CLOSE POSITION
FOR 52 CB /BAYCIRCUIT
BREAKER FOR LOCAL OPERATION:
1.89-A ISOLATOR OPEN CONDITION.
2.89-L ISOLATOR OPEN
CONDITION.
3.89-AE TBC EARTH
SWITCH CLOSED CONDITION.
4.89-LE1 EARTH SWITCH CLOSED CONDITION.
TRANSFER BUS COUPLER
FOR 89-A / TBC ISOLATOR OPERATION:
1.52 CB / TBC IN OPEN CONDITION.
2.89AE / TBC EARTH SWITCH OPEN CONDITION.
3.BB189E BUSEARTH SWITCH OPEN CONDITION.
4.89-B/TBC ISOLATOR OPEN CONDITION
( Selection Logic Considering BC Isolator & BC CB can be opt , for online switching between BUS- 1& 2)
FOR 89-B / TBC
ISOLATOR OPERATION:
1.52 CB / TBC IN OPEN CONDITION.
2.89AE / TBC EARTH SWITCH OPEN CONDITION.
3.BB289E BUSEARTH SWITCH OPEN CONDITION.
4.89-A/TBC ISOLATOR OPEN CONDITION
( Selection Logic Considering BC Isolator & BC CB can be
opt , for online switching between BUS- 1& 2)
FOR 89-C / TBC
ISOLATOR OPERATION:
1.52 CB / TBC IN OPEN CONDITION.
2.89CE / TBC EARTH SWITCH OPEN CONDITION.
3.BB389E BUSEARTH SWITCH OPEN CONDITION.
FOR 89-AE / TBC EARTH
SWITCH OPERATION:
1.89-A / TBC ISOLATOR OPEN CONDITION.
2.89-B / TBC ISOLATOR OPEN CONDITION.
3.52-CB / TBC BREAKER OPEN CONDITION.
FOR 89-CE / TBC EARTH
SWITCH OPERATION:
1.52-CB/ TBC BREAKER
OPEN CONDITION.
2.89-C / TBC ISOLATOR OPEN CONDITION.
FOR 52 CB / TBC
CIRCUIT BREAKER FOR REMOTE OPERATION:
1.86-GA / TBC HSTR/MTR RESET CONDITION.
2.86-GB / TBC HSTR/MTR RESET CONDITION.
3.96-BB / TBC HSTR/MTR RESET CONDITION.
4.89A/89B ISOLATOR CLOSE POSITION
5.89C ISOLATOR CLOSE POSITION
FOR 52 CB / TBC
CIRCUIT BREAKER FOR LOCAL OPERATION:
1. 89-A / TBC ISOLATOR OPEN CONDITION.
2. 89-B / TBC ISOLATOR
OPEN CONDITION.
3. 89-C / TBC ISOLATOR OPEN CONDITION.
4. 89-AE / TBC EARTH
SWITCH CLOSED CONDITION.
5. 89-CE / TBC EARTH
SWITCH CLOSED CONDITION.
FOR 89-A / BC
ISOLATOR OPERATION:
1.52 CB / BC IN OPEN CONDITION.
2.89AE / BC EARTH SWITCH OPEN CONDITION.
3.BB189E BUSEARTH SWITCH OPEN CONDITION.
FOR 89-B / BC
ISOLATOR OPERATION:
1.52 CB / BC IN OPEN CONDITION.
2.89BE / BC EARTH SWITCH OPEN CONDITION.
3.BB289E BUSEARTH SWITCH OPEN CONDITION.
FOR 89-AE / BC EARTH
SWITCH OPERATION:
1.89-A / BC ISOLATOR OPEN CONDITION.
2.52-CB / BC BREAKER
OPEN CONDITION.
FOR 89-BE / BC EARTH
SWITCH OPERATION:
1.89-A / BC ISOLATOR OPEN CONDITION.
2.52-CB / BC BREAKER OPEN CONDITION.
FOR 52 CB / BC
CIRCUIT BREAKER FOR REMOTE OPERATION:
1.86-GA / BC HSTR/MTR RESET CONDITION.
2.86-GB / BC HSTR/MTR RESET CONDITION.
3.96-BB / BC HSTR/MTR RESET CONDITION.
4.89-A/BC ISOLATOR
CLOSE POSITION
5.89-B/BC ISOLATOR CLOSE POSITION
FOR 52 CB / BC
CIRCUIT BREAKER FOR LOCAL OPERATION:
1. 89-A / BC ISOLATOR OPEN CONDITION.
2. 89-B / BC ISOLATOR
OPEN CONDITION.
3. 89-AE / BC EARTH SWITCH CLOSED CONDITION.
4. 89-BE / BC EARTH SWITCH CLOSED CONDITION.