Most of the transformers installed in various area
substations are supplied by Voltamp.
Some of the main fittings and accessories
of these transformers are :
TAP CHANGING ARRANGEMENT:
Off-Circuit Switch
The
transformer is normally fitted with an off circuit tap changing switch to
obtain required voltage ratio. It can be hand operated by a switch handle
mounted either on tankl cover or on the tank side.The locking devices is fitted
to the handle to lock in any lock position. The switch mechanism is such that
it can be locked only when it is located in its proper position and not in any
intermediate position.
THE
TRANSFORMER MUST BE ISOLATED FROM ALL THE LIVE LINES, BEFORE OPERATING THE
SWITCH.
Operating the switch when transformer is energized, will
damage the switch contacts due to severe arcing between the contacts and may
damage transformer winding.
When the switch handle is provided on the side wall,
it is necessary that Switch handle assembly is dismantled before untanking.
Off-CircuitRatio Changing Links
Sometimes links are provided inside the transformer tank to obtain required voltage ratio. Links are required to be loosened and fixed in new required position as given in name plate. Links are accessible from the inspection cover. In case of conservator units, oil level has to be lowered below the inspection cover before unbolting inspection cover.
Sometimes links are provided inside the transformer tank to obtain required voltage ratio. Links are required to be loosened and fixed in new required position as given in name plate. Links are accessible from the inspection cover. In case of conservator units, oil level has to be lowered below the inspection cover before unbolting inspection cover.
On-Loading Tap Changer
The on-load tap changer is an optional fitting. The
on-load tap changers are provided with local manual control, local electrical
control and remote electrical control. The automatic voltage regulation can
also be provided as optional fittings.
The
tappings are located on high voltage winding.
For
further details, please refer to the attached manual of OLTC and schematics.
Earthing Terminals
The core laminations assembly is connected to core
clamping frame which is in turn connected to the tank. Two earthing terminals
are provided on the transformer tank. The earhing terminals should be connected
to the earthing.
Lifting Lugs
Two/Four fittings lugs of adequate capacity are
provided on tank sides/top cover to lift
fully assembled transformer filled with oil.
All lugs are designed for simultaneous use and must be
used accordingly. Two/Four lifting lugs are provided for untaking the core and
windings of larger capacity transformers.
All heavy fittings are also provided with individuals
lifting lugs.
Valves
Every transformer is provided with drain cum filter
valve at bottom of the tank, and filter valve at top of the tank. Valves are
fitted with plugs/blanking plates to stop oil coming out.
Mainly two types of valves are provided:
1.
Wheel Valves
2.
Butterfly valves
The wheel valves are used either with female screw threads or with flanges. These are of
gun-metals/cast iron type’s
Generally, one Isolating Valve also known as shut off
valve is provided for transformer upto 2000 KVA between conservator and
buchholz relay.
The Butterfly type cast-steel valves with the machined
flanges are used at points of connection between tank and detachable radiators.
BUSHINGS
Oil Communicating Type
Transformers windings are connected to the external
circuit through terminal bushings. The bushings are installed on the cover or,
on side walls of the transformer tank. The lower end of the bushing protrudes
into the tank and at both their ends are provided with suitable fasteners to
connect the line leads inside the transformers
an external conductors outside it.
The shape and size of the bushings depend on the
voltage class, type of current. Electrical performance of these bushings
conform to I.S. 2099 & I.S. 7421
Dimensional details and associated parts generally conform to IS-3 upto 36 KV class. Bushings of 1000Volts are of two piece constructions
without arcing horns, whereas all other bushings are of single piece porcelain
type. Assembly and dismantling of single tank cover is required to be removed for
necessary access to the inner (lower) end of the bushings. These bushings are
not detached at the time of transportation.
Condenser
Bushings
Generally, condenser bushings are used for 72.5 KV and above. These bushings
contain their own oil and are sealed to retain the same. Whenever these
bushings are mounted on bushing pockets or raised truncated portions, air vent
pipes are provided for carrying away air or gases from these pockets to Buchholz
relay during service typical assembly is shown in flg.5.
These bushings are detached from the transformers and
dispatched separately, they are packed as per manufacturers instructions. The
draw through type lead is coiled and kept temporarily below the bushing
blanking plate. The equipment required for mounting the bushings are (i) rope
slings (ii) flexible steel wire approx 2mm in dia, of suitable length,
Typing procedure for mounting is as follows:
(i)
Open the bushing
case carefully and check it for transit damage and clean the bushing
thoroughly.
(ii)
Check whether the
gasket on the pocket is in order. If not, clean the seat of the gasket and
replace it by new one.
(iii)
Remove the
locating pin (3).the cable bolt to be used on the unit is brazed to the end of
the flexible draw through type lead mentioned above.
(iv)
Removing the
blanking plate and uncoil the draw through type lead. Tie the flexible steel
wire to the head of the bolt fixing temporarily on the top of the cable bolt(2)
to facilitate the threading of the main lead through the bushing tube and at
the same time preventing the lead
form falling back into the tank.
(v)
Suitably raise
the bushing and remove the protective cover at the oil end of the bushing.
(vi)
Check that Oil level
in the bushing is appearing in the Oil Level Indicating glass. In case it is
not visible, do not mount that bushing. Also do not attempt to oil fill at site
as such bushing is most likely to failure in service.
(vii)
During the lowering operation, thread the
flexible steel wire through the inside tube of the bushing and pull it.
Continue the operation till the bushing rests on its flange pocket. Bolt the
two flanges and revove the slings.
(viii)
Hold the cable
bolt in position, remove the flexible wire and insert the locking pin (3) to
hold the cable bolt remove the slings.
(ix)
Fix the terminal
cap (1) in position by screwing it on the terminal bolt.
(x)
For removing air
from the central tube after oil filling, unscrew the terminal cap and press the
terminal bolt downward.
(xi)
Fix upper and
lower arcing horns and adjust the gap setting as per the required Insulation
Co-ordination.
Cable Boxes
Cable boxes are designed for receiving and protecting
cable ends. Insulating paper is most hygroscopic
and all paper insulated cable ends must be protected by suitable insulating Compound
.These cable boxes are provided with brass wiping glands and are designed with Clearance
inside the box suitable for compound filling. The cable box in such case must
be Filled with compound as marked as indicated in the drawing.
Cable boxes for PVC or XLPE cables are designed with
air clearance and hence these boxes are not required to be filled with
compound.
Cable boxes of 3.6 KV and above are provided with
detachable gland plates. Earthing terminals are also provided on these cable
boxes for earthing the armouring of individual cable.
When cable boxes are provided with disconnecting
chambers they permit removal of Transformers for servicing without disturbing
cable terminations.
Bus-Duct/Trunkings
Some users prefer connections to load by means of
Bus-Duct. Bus duct is supplied by some other Agency. However, we provide
suitable flanges.trunkings around transformer bushings for receiving the
busduct.
The level of the busduct flanges from groud/rail level
is indicated in the General Arrangement Drawings of the transformer. The
complete details busduct flange is
furnished by us giving complete dimensional details for the matching flanges,
bolt spacing, bushing terminal details etc.
Marshalling
Box
The transformer
is provided with certain fittings directly mounted on the transformer at
various locations. These fittings are having electrical contacts or terminals
which are required to be connected to the protection schemes to give
alarm/annunciation under abnormal
conditions and if further required to disconnect the transformer form mains. In
order to facilitate connections of all such devices to the protective scheme, the
cable form all such contacts are wired upto a weather proof terminal box. This box called Marshalling
Box, is also used for housing Oil Temperature Indicator (OTI) and Winding
Temperature Indicator (WTI).
The Marshalling box is made of sheet Metal and is
provided with glass window for observing OTI & WTI.
It has hinged door with locking facility to prevent
unauthorized access. The capillaries from OTI &WTI come out from the bottom
of the Marshalling box through suitably recessed gland plate thus preventing
ingress of dust.
It has detachable gland plate with glands through
which cables enter and leave. It has a rain shed provided on top to prevent
rain falling directly over it. All these provisions make Marshalling Box a
Weather-proof enclosure.
Buchholz
Relay
Buchholz relay is a very sensitive, gas and oil
operated apparatus which detects formation of gas or development of sudden
pressure inside the oil filled transformer. It is connected to protection
circuits to give an early audible alarm of gas collection and to disconnect the
transformer from supply in case of sever fault inside the transformer.
The basic function of the relay, is to initiate an
electrical signal in the protection circuit when:
(a) Gas is accumulated in the relay, as result of
incipient fault.
(b) Surge of oil is developed on account of sudden
increase in pressure inside the transformer due to sever fault.
(c) Oil level in the relay is reduced below the minimum
level.
Buchholz relay operates in the following manner:
The relay comprises a housing containing two pivoted
buckets/Floats counter balanced by dead weights. Each bucket assembly carries a
mercury switch. The relay is fitted in
the oil connection between conservator and tank.
Due to gas collection, the oil level inside the relay
drops and the upper bucket moves down. This tilts the mercury switch brining
fluid mercury in such a position that it bridge the normally open (NO)
contacts. Other probable reasons for droping of level in the relay are:
(a) Leakage of oil from main tank, conservator or relay
itself.
(b) Collection of air in the relay which is trapped
earlier in the tank and in the winding.
The lower bucket operates similar to upper bucket when
level in the relay drops further. However important function of this relay is
to disconnect transformer from circuit under sudden development of pressure
inside the transformer doe to severe internal fault In such cases, gas
generation is rapid and displaced oil surges through the relay impinge on the
baffle plates causing lower bucket to tilt and close the Normally Open (NO)
contact of the mercury switch carried by it.
Upper bucket contacts are connected to audible alarm-‘A’-
circuit and lower bucket contacts-‘T’- are connected to trip circuit.
The relay is mounted in position with associates
piping and Isolating valves at works. In larger transformers, the buchholz
relay assembly is dismantled and sent separately. When Test Lever is provided,
it is sent in ‘Test’ position to prevent damage to window glasses and mercury
switches.
Mount the Buchholz relay between conservator and
transformer tank cover along with piping and valves without straining the pipe
line. Isolating valve must be fully opened after mounting is completed
To ensure successful operation of the relay the pipe
work on either side of the relay is set inclined to horizontally by 3-50.
MOUNT RELAY SUCH THAT ARROW DIRECTION POINTS TOWARDS
CONSERVATIOR
After filling oil in the transformer, air trapped inside
the relay is to be released through the valve/petcock provided on top of
buchholz collection, it must be ensured that this valve is kept open and the
pipe is full of oil. When gas is collected, oil from pipe will flow out first
and then gas will come out.
Radiators
The function of radiators is to limit the temperature
of oil and winding by dissipating heat that is generate due to the losses
within the transformer while in the service. The number of sections per
radiator and the number of radiators per transformer will depend upon the
losses and permissible temperature rise.
Distribution Transformers are normally provided with
radiators welded to tank. Owing to transport limitation and possible transit
damages, power transformers are provided with detachable radiator with radiator
valves in position on tank flanges.
-
Each radiator consists
of number of “Section” made from pressed CRCA Sheets forming channels for oil
flow. These “Sections” are welded to Header Pipes at Top and Bottom. Detachable
radiators are provided with M.S. Flanges
at Top and Bottom. Flanged radiators are fitted with Air Release Plug, Drain
Plug and Lifting Lug.
-
Bracing Straps,
made from M.S. Flat are provided on radiator to prevent vibration of section.
Radiators are cleaned internally to remove scales and
a coat of varnish is applied. External surface cleaned off all rust and one
coat of Red-Oxide primer is applied which is followed by final painting.
Silica Gel
Breather
Whenever there is a change in the ambient temperature
or in the load of an oil immersed transformer there is a change in oil pump,
& hence in the volume of oil. Increase in oil volume, casuses the air above
the oil level in the conservator to be pushed out and decrease causes air to be
drawn in. Thus the transformer “Breathes”. When air is breathed in , there is a
possibility of moisture and dust from atmosphere to be sucked in. These
contaminants deteriorate the insulation properties of oil. Hence, Silica Gel
Breather is provided which arrests moisture and dust from the air drawn in.
A Typical- Silica Gel Breather has following main
components:
1. A Casing
2. Silica Gel Crystal
3. An oil Seal at the lower end of casing
The casing has a window at the upper part for
observation of the color of the Gel crystals. It has flange connection at the
top for the connecting the breather to the breather pipe. The lower part of the
casing has at its lower end an oil seal arrangement, a window for observation
of oil level and an oil filling hole with gasket and plug.
Due to the chemical affinity possessed by Silica Gel
Crystals, they absorb moisture from the air drawn in. The color of silica gel is
blue when dry and turns pink when it is saturated with moisture. The color of
crystal can be observed from the outside of the casing.
Oil seal assembly at the lower end of the casing
consists of little quantity of oil with an inverted cup
Partly dipped in the oil and a tube fixed at the
center of the cup.
The oil acts as
a coarse filter and removes the dust from the outside air when it is
passes through oil.
Silica gel breather is depatched in a separate case.
Magnetic Oil
Level Gauge (MOG)
This is a dial type oil level indicating device
provided on larger transformers with conservator at relatively high levels from
the ground. In large transformers conventional glass oil level indicators are
difficult to observe due to their heights and color change/dust accumulation on
the glass. Further, the low oil level in the conservator falls to a low level.
This protection feature and clear visibility justify the cost of MOG on a
bigger transformer.
It consists of two compartments:
1.
The oil side
compartment which fixed on the opening in the conservator.
2.
The pointer side
compartment.
These compartments are sealed against leakage of oil
by a metallic diaphragm. On the oil side compartment, there is a bevel gear
wheel and it is positioned near the diaphragm. Movement of the float due to
rise and fall of oil level in the conservator results into circular motion of
the driving magnet. A follower magnet is positioned in the pointer side
compartment near the diaphragm. This magnet has its poles face to face poles of
driving magnet from the oil side compartment coupling them magnetically. The
movement of float is, therefore, transferred through the diaphragm, eliminating
direct oil light mechanical coupling.
At the other end of the axis of the driven magnet an
indicating pointer is fitted. The dial is calibrated to show the oil level in
the conservator. The dial and the pointer area housed behind the front glass.
The dial has three position marked. The follower magnet has also a cam fitted
on it which operates a mercury switch. When this magnet is at a position
corresponding to low oil level the mercury switch closes the Normal Open (NO)
contacts. These contacts are normally wired
to give audible alarm. The contacts are brought to terminal box at the lower
end of the dial, for external connection.
Oil
Temperature Indicator (OTI)
-
Oil Temperature
Indicator (OTI) is generally provided on all transformers except for very small
ratings. The direct reading pointer arrangement in this instrument greatly
facilitates observation of working temperature of oil. It also helps, if need be,
in deciding the permissible overloads in accordance with I.S. 6600-1972. Guide for
loading of oil immersed transformers.
-
A Typical-Oil
temperature indicator consists of a
-
Bourdon tube with
a pointer arrangement mounted in a case comprising of a reading dial and a
glass cover. There is a temperature sensing bulb which communicates to the
Bourdon tube through the armoured capillary.
-
The oil
temperature indicator is provided with two pointers and associated contacts for
protection of transformers. Both the pointers are independently adjustable and
can be set to desired temperature. Setting of these pointers at required
temperatures can be done from outside through the knob by using special keys.
-
The OTI is
generally housed and wired upto terminal strip in the Marshalling box having a
glass window on the door for observation. The length of capillary does not
influence the accuracy of measurement and extra length of capillary tubing must
not be cut, as it would be break communication between bulb and Bourdon tube.
If the oil temperature increases beyond set limit due
to overload or inadvertent closure of radiator valves or insufficient air draft,
the indicating pointer touches the present alarm pointer and actuates the alarm
contact. The alarm contacts, when duly wired give an alarm. If the alarm is not
attended and there is a further increase of temperature, the trip contacts
which are wired to the trip circuit will operate and isolate the transformer
form mains.
Winding
Temperature Indicator (WTI)
A winding temperature indicator (WTI) is an optional
fitting and is provided when ordered. It is set to read Hot Spot Temperature
(HST).
A typical WTI arrangement comprises of the following:
(a) WTI instrument having a temperature sensing bulb
and a capillary similar to OTI. In addition it is provided with a heater coil
around its operating bellow.
(b) A current transformer mounted on one of the
transformer leads, sensing load current.
The bulb of the instrument is placed in an oil filled
pocket located on the top cover of the transformer similar to OTI pocket. The
Heater Coil is fed by the W.T.I.C.T.
Thus the Temperature indicated by WTI accounts for
(i)
Temperature of Top
Oil and
(ii)
Winding Gradient
( Temperature Rise of winding over surrounding oil) which is dependent on load
Current.
And is adjusted
to read HST = [Top oil Temp.] + 1.1 x Gradient
The Heater Coil is provided with an adjustable
resistive shunt. (Ref fig. 24) in parallel which allows the instrument to be
adapted for a range of winding Gradients
The adjustable shunt by-passes certain amount of
current (ISH) from the C.T. Secondary Current (IS). Thus Heater Coil current
IH = IS - ISH
For the particular transformer, the shunt is
adjusted at factory for the applicable
Winding Gradient. WTI also has Alarm & Trip Contacts. Foe Fan Cooled
Transformers auxiliary contacts of WTI are used for Fan switching.
Repeater OTI
& WTI Instruments
Repeater OTI & WTI instruments are Optional
Fittings and are provided when ordered. They enable readings being taken in control
room also. They are generally provided in the RTCC Panel, when it is a part of
contact.
They are available in one of the following types:
(a) Simple Analog
Repeater
(b) 4-20mA. d.c. Analog Repeater
(c)
4-20mA. d.c. Digital Repeater
(d) 4-20mA. d.c.
Digital Repeater plus signal for SCADA
They all require the Local Instrument to be provided
with a precision potentiometer.
In cases (b), (c), & (d), they also require
Auxiliary Devices like Power Supply Unit, Resistance to
Current Converter (RCXT) and/or Current to Current
Converter (CCXT) etc. They are housed in a UNIT BOX mount on the transformer.
Wiring Diagrams and Interconnection Diagrams necessary
for the wiring of Marshalling Box, UNIT BOX and RTCC Panel are supplied along
with transformer.
OTI &
WTI Instruments Operated By Resistance Temperature Detectors (RTDs)
Temperature sensing can alternatively be done by
Resistance Temperatures Detectors (RTDs). Thus OTI & WTI can be operated by
RTDs. When, so ordered, they are provided accordingly. In this case also Power
Supply Unit and RCXT Unit will be required and they are provided in the Unit
Box.
Here again Repeater Instruments are provided when
ordered.
Thermesyphon
Filter: (Ref. Fig. 26) Thermosyphons
Thermosyphon Filter is devices which continuously
improve the quality of oil in the transformer tank. It is an optional fitting
and is provided when ordered.
It is a container having perforated trays filled with
Activated Alumina. It is fitted to the transformer tank similar to a radiator with
provision of isolating valves, air release plug, drain valve etc. Due to the convection
current set up in oil, oil flows continuously over the exposed surface of
Activated Alumina (i.e. the adsorbent material) and in the process,
contaminants like moisture, organic acids etc. generated due to ageing of insulation, get collected in the
adsorbent material and thus improve the quality of oil.
Periodic recharging of adsorbent material is
necessary.
Flexible
Separator (Ref. fig. 27)
Also known as ‘Diaphragm Conservator’ or ‘Rubber
Diaphragm’. It is an optional fitting and is provided when ordered.
The ‘Flexible Separator’ is sealed, nonporous flexible
bag of a highly resistant fabric, coated externally to resist transformer oil
and internally to resist external atmosphere.
It is fitted inside the conservator such that
variations in oil volume due to variations of temperature are taken up by the Flexible
Bag. Oil in conservator is sealed from the outside atmosphere by the mounting
flanged to which the Flexible Bag is attached. Thus the atmospheric moisture
and gases cannot contaminate the oil inside the conservator.
Fig. (a) Shows the separator in inflated condition
corresponding to low oil volume. When oil expand due to increase in
temperature, atmosphere inside the separator is exhaled and the separator bag
deflates as shown in Fig. (b).
Oil filling in the conservator is to be done as per
the procedure given in 2.20
Oil Level
Transmitter: (fig. 28)
When oil in conservator is to be remotely monitored
Oil level transmitter is to be provided. It is an optional fitting and is
provided when ordered.
Transmitter System comprises of:
(i)
Stainless Steel
Rod which goes inside the conservator tank.
(ii)
Transducer which
gives electrical signaldepedent on the oil level.
(iii)
Power Supply/V-I
Module which provides 4-20mA signal from the transducer output.
On Load Tap
Changer (OLTC): (Ref. Flag. 22&23)
OLTC is an optional device and is provided when ordered.
Tapings are located on High Voltage Winding of the
transformer.
One type of OLTC is fitted external to transformer
main tank . In the other type, contacts mounted on insulated cylinder are
immersed in the transformer main tank. In both the types, Drive Mechanism (DM)
contained in a separate box.
Different arrangements used to effect tap changing . They
are:
(a) Linear: Commonly used arrangement when no of tap
positions is moderate.
(b) Coarse/Fine: By means of a changer over contacts, the
Coarse tap winding is included in or
excluded from the circuit. Thus two voltages (i.e. tap positions) are obtained
for one position of moveable arm.
(c) Reverse/Forward:
By Means of a changer-over contact, the taping winding is connected in Forward
(Adding) or Reverse (i.e. Subtracting) direction w.r.t. main winding. Thus two
voltages (i.e. tap positions) are obtained for one position of moveable arm.
Arrangement (b) & (c) used when no. of tap
positions is large.
OLTC is generally operated electrically through a
Remote Tap Control Cubicle (RTCC) located in Control Room. A electrical control
is also provided in the DM, along
with a selector switch for Local or Remote Control. For emergency manual
operation, an operating Handle is provided.
When Automatic Voltage Regulating (AVR) Relay is ordered and a Voltage Transformer (V.T.) is wired on
the transformer output side, the output
voltage is compared in the AVR Relay with the suitable reference voltage
and difference used to give command to OLTC so as to reduce the difference.
Thus the output voltage is automatically controlled to the preset value.
A Line Drop Compensator (LDC) is included in the AVR
when specially ordered R&X of the
cable, connecting transformer to load, are
to be set by means of adjustable knobs
In such a case; voltage at the end of of the cable and not a transformer terminals, is controlled.
Direction of Power Flow is an important consideration
in OLTC. Only some types are suitable for Full Power Flow in –terms of current
and no. of operations in the reverse direction. These details are given in the
plate fitted to OLTC.
2 comments:
I found this informative and interesting blog I think it’s very useful and knowledgeable. I would like to thank you for the efforts you have made in writing this article.
HV Test Equipment Hire
Very informative blog. very useful information. thank you for sharing.
Power Transformers in India | Transformer Manufacturer in India
Post a Comment