Distance
protection relay- Before going
to Distance Protection Relay First see what is Protection System in Power
System & Transmission Lines.
·
The purpose of
protective relays and system is to operate the correct CB so as to disconnect
only the faulty Equipment/Ckt. From the system as quickly as possible, Thus
minimizing the trouble & damage caused by fault when they do occur.
·
Most faults
are shunt faults which are characterize by increase in current, reduction in
voltage, power factor & frequency.
Primary &
Backup Protection
·
Primary relaying
or also called Group-1, Main-1 or Stage-1, the function of this is first line
of defense for protecting the eq. whereas the backup relaying (Group-2, Main-2
or Stage-2) works only when primary relaying fails.
·
Time delay and
relay settings of backup relays are higher than the primary relays.
·
In distance
protection Characteristics are also different for both primary & backup
relays.
Understanding
Distance Protection & distance protection relay
Why Distance
Protection
> Since the impedance of a transmission line is
proportional to its length, for distance measurement it is appropriate to use a
relay capable of measuring the impedance of a line up to a predetermined point
(the reach point). Such a relay is described as a distance relay and is designed
to operate only for faults occurring between the relay location and the
selected reach point, thus giving discrimination for faults that may occur in
different line sections.
> The basic principle of distance protection
involves the division of the voltage at the relaying point by the measured
current. The apparent impedance so calculated is compared with the reach point
impedance.
If the measured impedance is
less than the reach point impedance, it is assumed that a fault exists on the
line between the relay and the reach point. The reach point of a relay is the
point along the line impedance locus that is intersected by the boundary
characteristic of the relay. Since this is dependent on the ratio of voltage
and current and the phase angle between them, it may be plotted on an R/X diagram.
The loci of power system impedances as seen by the relay during faults, power
swings and load variations may be plotted on the same diagram and in this
manner the performance of the relay in the presence of system faults.
DISTANCE
PROTECTION RELAY CHARACTERISTICS
Some numerical relays measure the absolute fault
impedance and then determine whether operation is required according to
impedance boundaries defined on the R/X diagram. Traditional distance relays
and numerical relays that emulate the impedance elements of traditional relays
do not measure absolute impedance.
They compare the measured fault voltage with a
replica voltage derived from the fault current and the zone impedance setting
to determine whether the fault is within zone or out-of-zone.
Impedance
Characteristics
Relay measuring elements whose functionality is
based on the comparison of two independent quantities are essentially either
amplitude or phase comparators.
For the impedance elements of a distance relay, the
quantities being compared are the voltage and current measured by the relay.
There are numerous techniques available for performing the comparison,
depending on the technology used. They vary from balanced-beam (amplitude
comparison) and induction cup (phase comparison) electromagnetic relays,
through diode and operational amplifier comparators in static-type distance
relays, to digital sequence comparators in digital relays and to algorithms
used in numerical relays.
Plain Impedance
Characteristic
This characteristic takes no
account of the phase angle between the current and the voltage applied to it;
for this reason its impedance characteristic when plotted on an R/X diagram
is a circle with its center at the origin of the co-ordinates and of radius
equal to its setting in ohms.
Operation occurs for all
impedance values less than the setting, that is, for all points within the
circle. The relay characteristic, shown in Figure 11.7, is therefore non
directional, and in this form would operate for all faults along the vector AL and
also for all faults behind the Bus bars up to an impedance AM. It
is to be noted that A is the relaying point and RAB is
the angle by which the fault current lags the relay voltage for a fault on the
line ABand RAC is the equivalent leading angle for
a fault on line AC. Vector AB represents the
impedance in front of the relay between the relaying point A and
the end of line AB. Vector AC represents the
impedance of line AC behind the relaying point. AL represents
the reach of instantaneous Zone 1 protection, set to cover 80% to 85% of the
protected line.
Disadvantages of
Impedance Char.
A relay using this characteristic has three
important disadvantages:
i. it is non-directional; it will see faults both in front of and behind the
relaying point, and therefore requires a directional element to give it correct
discrimination
ii. it has non-uniform fault resistance coverage
iii. it is susceptible to power swings and heavy loading of a long line, because
of the large area covered by the impedance circle.
Impedance relay
with Directional element
·
Directional
control is an essential discrimination quality for a distance relay, to make
the relay non-responsive to faults outside the protected line. This can be
obtained by the addition of a separate directional control element.
The impedance characteristic
of a directional control element is a straight line on the R/X diagram,
so the combined characteristic of the directional and impedance relays is the
semi-circle APLQ shown in Figure below:
Mho Relay
The mho impedance element is generally known as
such because its characteristic is a straight line on an admittance
diagram. It cleverly combines the discriminating qualities of both reach
control and directional control, thereby eliminating the ‘contact race’
problems that may be encountered with separate reach and directional control
elements. This is achieved by the addition of a polarising signal. Mho
impedance elements were particularly attractive for economic reasons where
electromechanical relay elements were employed. As a result, they have been
widely deployed worldwide for many years and their advantages and imitations
are now well understood. For this reason they are still emulated in the
algorithms of some modern numerical relays.
·
The characteristic
of a mho impedance element, when plotted on an R/X diagram,
is a circle whose circumference passes through the origin, as illustrated in
Figure (b).
This demonstrates that the
impedance element is inherently directional and such that it will operate only
for faults in the forward direction along line AB.
The impedance characteristic
is adjusted by setting Zn, the impedance reach, along the diameter
and ϕ, the angle of displacement of the diameter from the R axis.
Angle ϕ is known as the Relay Characteristic Angle (RCA). The relay
operates for values of fault impedance ZF within
its characteristic.
Third zone and bus
bar back-up zone
·
In this
application it is used in conjunction with mho measuring units as a fault
detector and/or Zone 3 measuring unit. So, with the reverse reach arranged to
extend into the busbar zone, as shown in Figure 11.10(a), it will provide
back-up protection for busbar faults. This facility can also be provided with
quadrilateral characteristics. A further benefit of the Zone 3 application is
for Switch-on-to-Fault (SOTF) protection, where the Zone 3 time delay would be
bypassed for a short period immediately following line energisation to allow
rapid clearance of a fault anywhere along the protected line.
Quadrilateral
Characteristic
·
This form of
polygonal impedance characteristic is shown in Figure 11.15. The characteristic
is provided with forward reach and resistive reach settings that are
independently adjustable. It therefore provides better resistive coverage than
any mho-type characteristic for short lines. This is especially true for earth
fault impedance measurement, where the arc resistances and fault resistance to
earth contribute to the highest values of fault resistance. To avoid excessive
errors in the zone reach accuracy, it is common to impose a maximum resistive
reach in terms of the zone impedance reach.
Recommendations in this respect can usually be
found in the appropriate relay manuals.
·
Polygonal
impedance characteristics are highly flexible in terms of fault impedance
coverage for both phase and earth faults. For this reason, most digital and
numerical distance relays now offer this form of characteristic.
Protection
Features of Numerical Distance protection relay
Phase and earth fault distance protection, each
with up to 5 independent
zones of protection. Standard and customised
signalling schemes are available to give fast fault clearance for the
whole of the protected line or cable.
> Directional earth fault protection (DEF)
·
Undervoltage
Protection
·
Overvoltage
Protection
·
Directional or
non-directional negative sequence overcurrent protection – This element
can provide backup protection for many unbalanced fault conditions.
·
Switch on to
fault (SOTF) protection – These settings enhance the protection applied for
manual circuit breaker closure.
·
Trip on reclose
(TOR) protection – These settings enhance the protection applied on auto
reclosure of the circuit breaker.
·
Power swing
blocking – Selective blocking of distance protection zones ensures stability
during the power swings experienced on sub-transmission and
transmission systems.
Non-Protection
Features of Distance protection relay
·
Autoreclosure with
Check synchronism ,
·
Measurements –
Selected measurement values polled at the line/cable terminal, available for
display on the relay or accessed from the serial communications facility.
·
Fault/Event/Disturbance
Records – Available from the serial communications or on the relay display
(fault and event records only).
·
Distance to fault
locator – Reading in km, miles or % of line length.
Zones of
Protection
Zone-1
The zone 1 elements
of a distance relay should be set to cover as much of the protected line
as possible, allowing instantaneous tripping for as many faults as possible. In
most applications the zone 1 reach (Z1) should not be able to respond to faults
beyond the protected line. For an underreaching application the zone 1 reach must
therefore be set to account for any possible overreaching errors. These errors
come from the relay, the VTs and CTs and inaccurate line impedance data. It is
therefore recommended that the reach of the zone 1 distance elements is
restricted to 80 – 85% of the protected line impedance (positive phase sequence
line impedance), with zone 2 elements set to cover the final 20% of the line.
Here: Ra = Relay at bus A, Rb = Relay at bus B,
Z1 = Zone-1 Reach for Relay Ra
= 80-85% Zab(Imp. Of Line AB),
Z2 = Zone-2 Reach for Relay Ra
= 120% Zab or Zab+(< 50% Zbc),
Z3 = Zone-3 Reach for Relay Ra
= 120%( Zab+Zbc),
Z4= Zone-4 Reach, reverse zone
reach for relay Ra= 10-25% of Zab or
Z4 ≥ ((Remote zone 2 reach,
Rb) x 120%) minus the protected line impedance
Zone-2
The zone 2 elements should be set to cover the 20%
of the line not covered by zone 1. Allowing for underreaching errors, the
zone 2 reach (Z2) should be set in excess of 120% of the protected line
impedance for all fault conditions. Where aided tripping schemes are used, fast
operation of the zone 2 elements is required. It is therefore beneficial to set
zone 2 to reach as far as possible, such that faults on the protected line are
well within reach. A constraining requirement is that, where possible, zone 2 does
not reach beyond the zone 1 reach of adjacent line protection. Where this is
not possible, it is necessary to time grade zone 2 elements of relays on
adjacent lines.
For this reason the zone 2 reach should be set to
cover ≤50% of the shortest adjacent line impedance, if possible. When setting
zone 2 earth fault elements on parallel circuits, the effects of zero
sequence mutual coupling will need to be accounted for.
The mutual coupling will result in the Zone 2
ground fault elements underreaching.
Zone-3
The zone 3 elements would usually be used to
provide overall back-up protection for adjacent circuits. The zone 3 reach (Z3)
is therefore set to approximately 120% of the combined impedance of the
protected line plus the longest adjacent line. A higher apparent
impedance of the adjacent line may need to be allowed where fault current can
be fed from multiple sources or flow via parallel paths.
Zone-4
The zone 4 elements would typically provide back-up
protection for the local busbar,where the offset reach is set to 25% of the
zone 1 reach of the relay for short lines (<30km) or 10% of the zone 1 reach
for long lines. Setting zone 4 in this way would also satisfy the requirements
for Switch on to Fault, and Trip on Reclose protection, as described in later
sections. Where zone 4 is used to provide reverse directional decisions for
Blocking or Permissive Overreach schemes, zone 4 must reach further behind the
relay than zone 2 for the remote relay. This can be achieved by setting:
Z4 ≥ ((Remote zone
2 reach) x 120%) minus the protected line impedance.
No comments:
Post a Comment