Why Earthing?
Earthing system is
a key element of electrical system. It is critical to ensure personnel safety
as well as to provide protection for equipment and to minimise interruption of
service.
Standard
Earthing is
carried out based on IEEE-80, IS:3043 and also by finite element method.
Input required?
–
Fault current & Duration
–
Ground current and fault clearing time
–
Soil resistivity
–
Area of the switchyard
Soil Resistivity Measurement
•
Resistivity test should be made to determine any
important variation of resistivity with
the depth of soil.
•
Resistivity test should be made at
number of places within the site. The
wenner’s four pin methods is the most commonly used technique. Four probes
are driven in to the earth along the straight line, at equal distance (A)
apart, driven to the depth (B). The voltage between the two inner electrodes is
then measured and divided by the current between the two outer electrodes to
give a value of mutual resistance R. Then,
Where,
r=
Resistivity of soil in W-m
R= resistance in ohms resulting from dividing the voltage between the
potential probes by the current flowing between the current electrodes.
A=Distance between adjacent electrodes.
B=Depth of electrodes in meter.
•
If B is small compared to A, as is the case of
probes penetrating the ground a short distance only, the above equation can be
reduced to
•
The current tends to flow near the surface for
small probe spacing, whereas more of the current penetrates deeper soils for
large spacing. Thus the resistivity measured for a given probe spacing A
represents the apparent resistivity of a soil to a depth of A.
•
The above derivation for the soil measurement is
based on the assumption that the soil resistivity is uniform. Uniform soil resistivity
means, soil resistivity remains constant both laterally and with depth to
infinity.
Variation of soil resistivity with moisure content
* Marginal moisure value is 20%
* The moisure will value decrease
35% to 10% at summer season
Earth Rod length
Earthing Design
•
Following aspects are checked while designing
earthing system
–
Adequacy of earthing conductor cross section
–
Grid size of the earthing conductor
–
Step potential and Touch potential
Cross section of
earthing conductor is to be sufficient to withstand the short circuit current.
Also while selecting the size corrosion allowance is taken into consideration.
In the switchyard
earthing conductors are laid forming a mesh. Usually the grid spacing is
uniform. But non-uniform grid spacing also can be adopted by calculation
earthing through finite element method.
Step Potential
Step Potential is the voltage difference between a person's feet cause
by the dissipation gradient of a fault entering the earth. Typically, one meter
from a fault entry point voltage reduced by 50%. (e.g. a 1000A fault entering
through ground impedance of 5 ohms. will create voltage of 5000V. At a distance
of less than one meter away a fatal potential of 2500V will exist). Earthmat
installed in that area will make the voltage gradient uniform and less than the
safety limit.
Touch Potential
Touch Potential is similar to step potential except that the part of
the fault current passes through the person's hand and body if he/she touches
any structure which is carrying fault current. Touch potential is eliminated by
connecting structure to the Earthmat so that least resistance path for fault
current is established.
Critical issues for earthing design
Earthing design becomes critical when…
•
Soil resistivity is high in rocky areas ( >
150 ohm-m )
•
High value of fault current and fault duration
•
Switchyard area is too small
•
Tolerable values of touch potential & step
potential
1 comment:
Thanks for Sharing this blog post with us. I would like to share that Paraflex is one of the leading house wire manufacturers. We are dedicated to safety, quality, and innovation as we produce, sell, distribute, and export premium wires for your homes and companies.
House Wire Manufacturers
Post a Comment