TESTING OF BUS POST INSULATOR




1. INSULATION  RESISTANCE MEASUREMENT  TEST
Insulation resistance of the BPI is to be taken for checking the healthiness of BPI. IR of the BPI need to check stack wise, i.e. top stack, middle stack, bottom stack etc. as same as LA with the help of 5 KV motorized megger. BPI has 3 stacks and we need to take 6 readings, of each stack and each stack to earth. The value should come greater than 10000 Mohm. 

2 comments:

High Voltage Commissioning said...

I found this informative and interesting blog I think it’s very useful and knowledgeable. I would like to thank you for the efforts you have made in writing this article.

High Voltage Commissioning

Louisville Kitchen Renovators said...

This blog appears to cover various topics in electrical engineering, and while I can't see the specific content of this post, I'm curious about your area of expertise within the field. Do you focus on a particular area of electrical engineering, such as power systems, control systems, or electronics design?