Capacitor Bank Protection
•
Over current and earth fault protection
•
Under voltage protection
•
Over voltage protection
•
Unbalance protection
Over current and earth fault protection
•
To guard against the faults on capacitor leads
between the circuit breaker and the units, it is normal to provide overcurrent
and earth fault protection using Inverse Minimum Definite Time (IDMT) Relay
•
A small time delay is provided to ensure that
these relays do not maloperate on capacitor “switching-in (inrush)” currents
•
When the source is earthed, two overcurrent and
one earth fault relays are used so as to cover both phase and earth faults
•
Instantaneous overcurrent units are not used as
they are liable to operate during normal switching condition (because inrush
current of very short duration flows during switching-in).
•
To limit the inrush current during
‘switching-in’ as well as overload current due to harmonics sometimes series
reactors are used with capacitor bank
Under-voltage Protection
•
During under-voltage conditions, the capacitor
will discharge into the system.
•
It is desired to trip the capacitor with a time
delay (time delay to prevent transient operation).
•
under-voltage relay for this purpose have a
setting of 30-90 % with built-in variable time delay and high reset ratio.
•
The incoming AC voltage on restoration will get
superimposed on to the remanent voltage and hence the over-voltage. To avoid
this a time delay between successive switching is provided so that the
capacitor will discharge to a safe value.
•
The time delay between successive switching is a
function of electrical system and capacitor voltage rating : say 1 minute for
415 V capacitor and 5 minutes for 11 kV capacitors
•
Hence timer is recommended for closing interlock
in each capacitor panel.
Over-voltage Protection
•
The capacitors are overstressed when subjected
to prolonged over-voltage condition.
•
This increases fatigue and shortens the life of
the capacitor.
•
The over-voltage is caused due to various
conditions: -
–
Increased bus voltage during lightly loaded
conditions due to Ferranti effect.
–
Harmonic over-voltage due to neighborhood of arc
furnace, thyristor controlled devices like convertors.
–
Switching surges
–
Transient over-voltages due to CB operating
mechanism including lightning
Unbalance Protection
•
Unbalance protection is provided either by
voltage or current measuring relays.
•
Voltage relays are generally applied to single
star with isolated neutral and delta banks
•
Current relays are applied to double star, delta
and single phase capacitor banks
Unbalance Protection for Delta Banks
•
In delta capacitor bank installations, the
unbalance protection can be provided by either current or voltage operated
relays
•
Unbalance voltage detection
–
The VTs are connected across any one of
identical series groups of each phase.
–
The secondaries of the VTs are connected in open
delta to feed the voltage relay.
Unbalance
voltage detection
•
Under normal healthy condition distribution of voltage
across each series group of the 3 phases are identical in magnitude, but 1200
displaced in phase. Hence the open delta output is zero.
When
the failure occurs in any one of the series groups of any phase, the voltage
distribution among the series groups of any phase is distributed, thereby
providing an open delta voltage to operate the relay.
Unbalance current detection
•
A CT is installed on the tie connection between
two parallel halves of each delta leg.
•
The CT from each leg is connected to a relay
•
A tunned relay along with a timer is
recommended.
•
The relay have a setting of 5-20 % or 10-40% of
rated current and time delay to prevent transient operation of the relay
Double star capacitor bank
•
For a double star capacitor bank with floating
neutral connection, a current relay operated off a CT in the floating neutral
connection is used.
•
Either definite time or inverse time relays can
be used for this application
•
The time delay must be provided to co-ordinate
with the fuse blowing time.
Neutral current detection
•
In case of grounded wye capacitor bank, CT is
installed in capacitor bank neutral to earth connection.
•
An unbalance in the capacitor bank say due to
failure of capacitor unit (s), causes current to flow in the neutral.
•
IDMTL relay connected across the CT secondary
operates and trips the bank.
Open delta voltage detection
•
An unbalance relay will be connected to
secondary of VTs (in open delta), the primary of which are connected across tap
points of the capacitor bank.
•
Under balanced conditions, the output of open
delta secondary is the addition of 3-phase voltages, which is zero.
•
When unbalance occurs due to failure of
capacitors, the voltage distribution across the series group varies in the
faulted phase. Hence the variation in the voltage of VT primary gives rise to
open delta secondary output to actuate the relay.
Single Phase Capacitor Banks
•
Single phase capacitor banks are generally used
for Railways applications
•
The protection for single phase banks are: -
–
Earth fault protection is provided by
differentially connecting the CTs on the phase and neutral side of the
capacitor bank
–
Over-current protection
–
Over-voltage protection
–
Under-voltage protection alongwith timer for
closing interlock
–
Unbalance protection
1 comment:
< MUST READ > ITS GOOD
Post a Comment